English Me connecter Je m'enregistre Parcourir le catalogue Contactez-nous
Expert mondial des câbles et systèmes de câblage

A propos de Nexans

Produits et Solutions

Service client

Carrières

Infos Presse

Ok

NA2XY

Envoyer le lien print
NA2XY Multi core, XLPE insulated, Aluminium conductor, PVC sheathed cable. Voltage rating 0.6/1kV.
Normes
Internationales  IEC 60502-1
Description

Construction

  • Aluminium Conductor
  • Insulation of cross-linked polyethylene (XLPE)
  • PVC sheath

 

ABREVATION:

N - Kabelmetal standard type

A - Aluminium conductor

2X - Cross linked PE (XLPE) insulation

Y - Polyvlin chloride (PVC) outer sheath

 

Application

For use in indoor intallations, in cable ducts/trays, in industrial plants, substations and power utility ditribution schemes. Installations underground with additional protection, where mechanical damage may be expected


 TOP
Caractéristiques
Caractéristiques de construction
Nature de l'âme Aluminium  
Isolation PRC  
Gaine extérieure PVC  
Caractéristiques électriques
Tension de service nominale Uo/U 0,6 / 1 kV  
Max. system voltage, 1-phase grounded 0,7kV  
Max. system voltage: 1 phase both phases grounded (Um) 1,2kV  
Max. system voltage 3 phases (Um) 1,2kV  
Caractéristiques d'utilisation
U.V resistance if required  
Non propagateur de l'incendie IEC 60332-3 Cat.A  
Facteur de courbure en cours de pose 10(xD)  
Minimum installation temperature 90°C  
Température maximale sur l'âme 90°C  
Température maximale sur l'âme en court circuit 250°C  

 TOP
Recherche Paramétrique
Nombre de conducteurs  
Diamètre extérieur approximatif  mm
Masse approximative  kg/km
Minimum Bending Radius - Install  in
Longueur  m
Intensité admissible enterré  A
Intensité admissible à l'air libre  A
Appliquer
Annuler
Votre sélection   11/11
Sélectionner tous les produits Code article Désignation du produit Nombre de conducteurs Diamètre extérieur approximatif (mm) Masse approximative (kg/km)
230437-00 NA2XY 4 x 16 4 19,5 385
230438-00 NA2XY 4 x 25 4 23,6 556
230440-00 NA2XY 4 x 35 4 22,2 663
230442-00 NA2XY 4 x 50 4 25,2 863
230443-00 NA2XY 4 x 70 4 29,0 1184
230444-00 NA2XY 4 x 95 4 32,2 774
230446-00 NA2XY 4 x 120 4 36,1 967
230447-00 NA2XY 4 x 150 4 39,5 1178
230448-00 NA2XY 4 x 185 4 44,4 1181
230450-00 NA2XY 4 x 240 4 49,7 1497
230452-00 NA2XY 4 x 300 4 55,0 1172
Ajouter aux favoris

 TOP
LIST OF AVAILABLE NA2XY 4 CORES

Aluminium Conductors, Cross-Linked PE (XLPE) Insulation,
Polyvinyl Chloride (PVC) Outer Sheath, 0.6/1kV cables.

Nominal 
Cross Sectional
Area

Number and 
Diameter of Wire

Nominal 
Overall 
Diameter

Maximum Permissible 
Current Rating 
Amp

Standard 
Delivery 
Length

Weight 
per Standard 
Delivery L

Delivery 
on Wooden 
Drum

mm²

No x mm

mm

In Ground @ 20°C

In Air @ 30°C

m

kg

 

4 x 16

7 x 1.70

19.5

87

77

1000

385

R12

4 x 25

7 x 2.14

23.6

111

97

1000

556

R14

4 x 35

7 x 2.58

22

134

120

1000

663

R14

4 x 50

19 x 1.83

25.2

160

146

1000

863

R14

4 x 70

19 x 2.20

28.7

197

187

1000

1184

R16

4 x 95

19 x 2.58

32.2

234

227

500

774

R16

4 x 120

37 x 2.08

36.1

266

263

500

967

R16

4 x 150

37 x 2.30

39.6

300

304

500

1178

R18

4 x 185

37 x 2.58

44.4

337

347

400

1181

R18

4 x 240

61 x 2.30

49.7

389

409

400

1497

R22

4 x 300

61 x 2.58

55

440

471

250

1172

R22


Maximum permissible current rating values stated for cables laid in ground are based on a load factors of 0.7 and for cables installed in air, aload factor of 1.0

 TOP
Information de livraison
The cable is to be wound on wooden drum in manufacturing length with -0% and +5% tolerance. Both ends of the cable on the drum shall be sealled to protect the cable from ingress of moisture.

Nexans © copyright 2001 - 2012   Notice Legale | Contactez nous | carte du site