A propos de Nexans
Produits et Solutions
Service client
Carrières
Infos Presse
ABREVATION:
N - Kabelmetal standard type
A - Aluminium conductor
2X - Cross linked PE (XLPE) insulation
Y - Polyvlin chloride (PVC) outer sheath
For use in indoor intallations, in cable ducts/trays, in industrial plants, substations and power utility ditribution schemes. Installations underground with additional protection, where mechanical damage may be expected
Aluminium Conductors, Cross-Linked PE (XLPE) Insulation, Polyvinyl Chloride (PVC) Outer Sheath, 0.6/1kV cables.
Nominal Cross SectionalArea
Number and Diameter of Wire
Nominal Overall Diameter
Maximum Permissible Current Rating Amp
Standard Delivery Length
Weight per Standard Delivery L
Delivery on Wooden Drum
mm²
No x mm
mm
In Ground @ 20°C
In Air @ 30°C
m
kg
4 x 16
7 x 1.70
19.5
87
77
1000
385
R12
4 x 25
7 x 2.14
23.6
111
97
556
R14
4 x 35
7 x 2.58
22
134
120
663
4 x 50
19 x 1.83
25.2
160
146
863
4 x 70
19 x 2.20
28.7
197
187
1184
R16
4 x 95
19 x 2.58
32.2
234
227
500
774
4 x 120
37 x 2.08
36.1
266
263
967
4 x 150
37 x 2.30
39.6
300
304
1178
R18
4 x 185
37 x 2.58
44.4
337
347
400
1181
4 x 240
61 x 2.30
49.7
389
409
1497
R22
4 x 300
61 x 2.58
55
440
471
250